G M WSC
PWS ID: TX2020067 · HEMPHILL, Texas 75948-0727
G M WSC serves 11,220 people in HEMPHILL, Texas using Surface Water water sources. It has 189 recorded EPA violations, including 133 health-based violations. PFAS "forever chemicals" were detected in UCMR5 testing (6 compounds found).
Water Quality Snapshot: G M WSC
G M WSC is a local-owned community water system that delivers drinking water to 11,220 residents in HEMPHILL, Texas (Sabine County) through 3,511 service connections. Its water is drawn from surface water sources. EPA's Safe Drinking Water Information System records 189 total violations for this system , of which 133 (70%) are health-based — meaning a contaminant exceeded an EPA Maximum Contaminant Level or a required treatment technique failed. A further 14 monitoring and reporting violations are on file. The most recent violation on record dates to 2024.
The most frequently cited contaminant at this system is TTHM, recorded in 61 violations (MCL, health-based). Under EPA's UCMR5 PFAS monitoring program, 6 PFAS compounds were detected in samples collected from this system, with a maximum reported concentration of 11.2 ppt. PFAS are persistent synthetic chemicals linked to health effects at very low exposure levels.
Across Texas, EPA tracks 7,351 public water systems serving 33,253,313 people, with 746,210 cumulative violations and 162,945 health-based violations on record. About 90% of systems in the state carry at least one violation, and state-wide the average per system is 101.5 violations. G M WSC's 189 violations sit above the Texas average. Statewide, 1,068 of 1,147 UCMR5-tested systems have reported PFAS detections (93.1%). All figures above are sourced directly from EPA SDWIS and UCMR5 public data releases and are updated as EPA publishes new reporting cycles.
6 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.
System Details
- System Type
- Community
- Owner Type
- Local
- Connections
- 3,511
- County
- Sabine
- School/Daycare
- No
- MCL Violations
- 117
- Monitoring Violations
- 14
- Treatment Tech Violations
- 16
Violation History
Contaminant violations recorded by EPA.
| Contaminant | Category | Count | Latest |
|---|---|---|---|
| TTHM | MCL | 61 | 2021 |
| Total Haloacetic Acids (HAA5) | MCL | 46 | 2016 |
| Coliform (TCR) | MCL | 10 | 2012 |
| Lead and Copper Rule | MR | 10 | 2020 |
| Public Notice | Other | 9 | 2022 |
| Interim Enhanced Surface Water Treatment Rule | TT | 8 | 2017 |
| LEAD AND COPPER RULE REVISIONS | RPT | 4 | 2024 |
| Revised Total Coliform Rule | TT | 4 | 2024 |
| LEAD AND COPPER RULE REVISIONS | TT | 4 | 2024 |
| Interim Enhanced Surface Water Treatment Rule | MR | 3 | 2016 |
| Coliform (TCR) | MR | 1 | 1992 |
| Coliform (TCR) | Other | 1 | 1992 |
PFAS Testing Results (UCMR5)
Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 13 of 540 samples detected PFAS.
| Contaminant | Date | Result | MRL | Status |
|---|---|---|---|---|
| PFTrDA | 7/19/2023 | <0.007 µg/L | 0.007 µg/L | Not Detected |
| PFDoA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFDA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFOA | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFOS | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFNA | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFHxS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHpA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFBS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NEtFOSAA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFHpS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFTA | 7/19/2023 | <0.008 µg/L | 0.008 µg/L | Not Detected |
| PFHxA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NMeFOSAA | 7/19/2023 | <0.006 µg/L | 0.006 µg/L | Not Detected |
| PFPeS | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFUnA | 7/19/2023 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| lithium | 7/19/2023 | <9 µg/L | 9 µg/L | Not Detected |
| NFDHA | 7/19/2023 | <0.02 µg/L | 0.02 µg/L | Not Detected |
| PFEESA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFMBA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFPeA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFMPA | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| 4:2 FTS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| 6:2 FTS | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFBA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| HFPO-DA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| ADONA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| 9Cl-PF3ONS | 7/19/2023 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| 8:2 FTS | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| 11Cl-PF3OUdS | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFHxS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFUnA | 7/19/2023 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| PFHxA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFDoA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFDA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFOA | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFHpS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFNA | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| ADONA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHpA | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFBS | 7/19/2023 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NMeFOSAA | 7/19/2023 | <0.006 µg/L | 0.006 µg/L | Not Detected |
| NEtFOSAA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFTrDA | 7/19/2023 | <0.007 µg/L | 0.007 µg/L | Not Detected |
| PFOS | 7/19/2023 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| 9Cl-PF3ONS | 7/19/2023 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| PFTA | 7/19/2023 | <0.008 µg/L | 0.008 µg/L | Not Detected |
| HFPO-DA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFBA | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| 6:2 FTS | 7/19/2023 | <0.005 µg/L | 0.005 µg/L | Not Detected |
Verify This Water System
The figures above are aggregated from EPA's public databases. To verify the underlying records — or to file a complaint, request a Consumer Confidence Report, or check current monitoring status — go directly to the federal and state regulators that enforce the Safe Drinking Water Act for G M WSC.
EPA SDWIS — Federal Reports
EPA's Safe Drinking Water Information System (SDWIS) holds the federal compliance record for every regulated public water system. Open the system-level report by PWS ID:
View PWS ID TX2020067 on SDWISSource: EPA SDWIS Federal Reports Search
Texas Drinking Water Authority
Texas Commission on Environmental Quality (TCEQ) — Drinking Water Watch is the primacy agency that licenses and inspects G M WSC under EPA-delegated authority.
Open TX regulator portalSource: Texas Commission on Environmental Quality (TCEQ) — Drinking Water Watch
Violation Timeline
Each row links to the EPA SDWIS public record for verification. Cross-reference the contaminant code on EPA's federal report to see violation dates, return-to-compliance status, and enforcement actions.
| Year (latest) | Contaminant | Category | Count | EPA Record |
|---|---|---|---|---|
| 2024 | LEAD AND COPPER RULE REVISIONS | RPT | 4 | SDWIS / TX2020067 / 5200 |
| 2024 | Revised Total Coliform Rule | TT | 4 | SDWIS / TX2020067 / 8000 |
| 2024 | LEAD AND COPPER RULE REVISIONS | TT | 4 | SDWIS / TX2020067 / 5200 |
| 2022 | Public Notice | Other | 9 | SDWIS / TX2020067 / 7500 |
| 2021 | TTHM | MCL | 61 | SDWIS / TX2020067 / 2950 |
| 2020 | Lead and Copper Rule | MR | 10 | SDWIS / TX2020067 / 5000 |
| 2017 | Interim Enhanced Surface Water Treatment Rule | TT | 8 | SDWIS / TX2020067 / 0300 |
| 2016 | Total Haloacetic Acids (HAA5) | MCL | 46 | SDWIS / TX2020067 / 2456 |
| 2016 | Interim Enhanced Surface Water Treatment Rule | MR | 3 | SDWIS / TX2020067 / 0300 |
| 2012 | Coliform (TCR) | MCL | 10 | SDWIS / TX2020067 / 3100 |
| 1992 | Coliform (TCR) | MR | 1 | SDWIS / TX2020067 / 3100 |
| 1992 | Coliform (TCR) | Other | 1 | SDWIS / TX2020067 / 3100 |
How G M WSC Compares
Cross-reference this system's record against state averages and the federal MCL framework for context.
| Metric | G M WSC | Texas avg | Federal benchmark |
|---|---|---|---|
| Total violations | 189 | 101.5 | SDWA compliance — any non-zero count is a recorded breach |
| Health-based violations | 133 | 22.2 | Indicates a contaminant exceeded a federal MCL |
| PFAS detection | 6 compounds | 93.1% | EPA final rule (2024): PFOA/PFOS MCL = 4.0 ppt |
| Population served | 11,220 | 4,524 | Sizing context for compliance burden |
Sources: EPA SDWIS and EPA National Primary Drinking Water Regulations (40 CFR Part 141). State averages computed across 7,351 regulated public water systems in Texas.
Federal MCL reference — Safe Drinking Water Act thresholds ▼
| Contaminant | Federal MCL / Action Level | Note |
|---|---|---|
| Lead | 0 mg/L (Action Level: 0.015 mg/L) | Lead and Copper Rule treatment technique |
| Arsenic | 0.010 mg/L (10 ppb) | Health-based MCL since 2006 |
| Total Coliform | Treatment technique (RTCR) | Indicator organism, monitoring trigger |
| PFOA / PFOS (PFAS) | 4.0 ppt each (final 2024 rule) | Compliance deadline 2029 |
| Nitrate (as N) | 10 mg/L | Acute health risk for infants |
Frequently Asked Questions
Is G M WSC water safe to drink? ▼
How many people does G M WSC serve? ▼
What type of violations does G M WSC have? ▼
Has PFAS been detected in G M WSC water? ▼
What water source does G M WSC use? ▼
Where does this data come from? ▼
Explore PlainWater
Related Data for Texas
Read our methodology — how this data is sourced, computed, and verified.