PlainWater

Community Water System · PWS TX0950004

Plainview Municipal Water System

Plainview, Texas 79072-8232 - drinking water served from surface water sources to 21,104 people, tracked in EPA SDWIS and UCMR5.

21,104
People served
22
EPA violations
11
Health-based
1 PFAS
UCMR5 result

The verdict

EPA records 22 drinking-water violations at Plainview Municipal Water System, 50% of them health-based - below the Texas per-system average, and UCMR5 testing detected 1 PFAS compound.

22
Total EPA violations on record
50%
Health-based (MCL / treatment failure)
21,104
People served by this system
1
PFAS compounds detected (UCMR5)

Water Quality Snapshot: Plainview Municipal Water System

Plainview Municipal Water System is a local-owned community water system that delivers drinking water to 21,104 residents in Plainview, Texas (Hale County) through 7,328 service connections. Its water is drawn from surface water sources. EPA's Safe Drinking Water Information System records 22 total violations for this system , of which 11 (50%) are health-based, meaning a contaminant exceeded an EPA Maximum Contaminant Level or a required treatment technique failed. A further 5 monitoring and reporting violations are on file. The most recent violation on record dates to 2017.

The most frequently cited contaminant at this system is Coliform (TCR), recorded in 7 violations (MCL, health-based). Under EPA's UCMR5 PFAS monitoring program, 1 PFAS compound was detected in samples collected from this system, with a maximum reported concentration of 5.3 ppt (parts per trillion). PFAS are persistent synthetic chemicals linked to health effects at very low exposure levels.

Across Texas, EPA tracks 7,351 public water systems serving 33,253,313 people, with 746,210 cumulative violations and 162,945 health-based violations on record. About 90% of systems in the state carry at least one violation, and state-wide the average per system is 101.5 violations. Statewide, 1,068 of 1,147 UCMR5-tested systems have reported PFAS detections (93.1%).

Plainview Municipal Water System's 22 violations sit below the Texas average.

All figures above are sourced directly from EPA SDWIS and UCMR5 public data releases and are updated as EPA publishes new reporting cycles.

PFAS Detected

1 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.

Population Served
21,104
Total Violations
22
Health-Based Violations
11
Water Source
Surface Water

System Details

System Type
Community
Owner Type
Local
Connections
7,328
County
Hale
School/Daycare
No
MCL Violations
11
Monitoring Violations
5
Treatment Tech Violations
0

Violation History

Contaminant violations recorded by EPA.

Contaminant Category Count Latest
Coliform (TCR) MCL 7 2010
Fluoride MCL 4 2004
E. COLI MR 4 2017
Public Notice Other 3 2010
Interim Enhanced Surface Water Treatment Rule MR 1 2005

PFAS Testing Results (UCMR5)

Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 1 of 348 samples detected PFAS.

Contaminant Date Result MRL Status
PFDoA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFEESA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
9Cl-PF3ONS 9/20/2023 <2.00 ppt 2.00 ppt Not Detected
ADONA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
NFDHA 9/20/2023 <20.00 ppt 20.00 ppt Not Detected
PFBS 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFHpA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFHxS 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFNA 9/20/2023 <4.00 ppt 4.00 ppt Not Detected
PFOS 9/20/2023 <4.00 ppt 4.00 ppt Not Detected
PFHpS 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFDA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFUnA 9/20/2023 <2.00 ppt 2.00 ppt Not Detected
HFPO-DA 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
PFBA 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
6:2 FTS 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
PFTA 9/20/2023 <8.00 ppt 8.00 ppt Not Detected
4:2 FTS 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
8:2 FTS 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
PFPeA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
NMeFOSAA 9/20/2023 <6.00 ppt 6.00 ppt Not Detected
NEtFOSAA 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
PFMBA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFOA 9/20/2023 <4.00 ppt 4.00 ppt Not Detected
PFMPA 9/20/2023 <4.00 ppt 4.00 ppt Not Detected
11Cl-PF3OUdS 9/20/2023 <5.00 ppt 5.00 ppt Not Detected
PFHxA 9/20/2023 <3.00 ppt 3.00 ppt Not Detected
PFPeS 9/20/2023 <4.00 ppt 4.00 ppt Not Detected
PFTrDA 9/20/2023 <7.00 ppt 7.00 ppt Not Detected
HFPO-DA 8/13/2024 <5.00 ppt 5.00 ppt Not Detected
8:2 FTS 8/13/2024 <5.00 ppt 5.00 ppt Not Detected
PFPeA 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
PFMBA 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
PFDA 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
PFDoA 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
NFDHA 8/13/2024 <20.00 ppt 20.00 ppt Not Detected
PFOS 8/13/2024 <4.00 ppt 4.00 ppt Not Detected
4:2 FTS 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
PFBA 8/13/2024 <5.00 ppt 5.00 ppt Not Detected
6:2 FTS 8/13/2024 <5.00 ppt 5.00 ppt Not Detected
PFOA 8/13/2024 <4.00 ppt 4.00 ppt Not Detected
PFPeS 8/13/2024 <4.00 ppt 4.00 ppt Not Detected
PFNA 8/13/2024 <4.00 ppt 4.00 ppt Not Detected
PFHpS 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
PFHxS 8/13/2024 <3.00 ppt 3.00 ppt Not Detected
NMeFOSAA 8/13/2024 <6.00 ppt 6.00 ppt Not Detected
NEtFOSAA 8/13/2024 <5.00 ppt 5.00 ppt Not Detected
PFTrDA 8/13/2024 <7.00 ppt 7.00 ppt Not Detected
PFMPA 8/13/2024 <4.00 ppt 4.00 ppt Not Detected
PFTA 8/13/2024 <8.00 ppt 8.00 ppt Not Detected

Verify This Water System

The figures above are aggregated from EPA's public databases. To verify the underlying records, or to file a complaint, request a Consumer Confidence Report, or check current monitoring status, go directly to the federal and state regulators that enforce the Safe Drinking Water Act for Plainview Municipal Water System.

Federal Source of Truth

EPA SDWIS, Federal Reports

EPA's Safe Drinking Water Information System (SDWIS) holds the federal compliance record for every regulated public water system. Open the system-level report by PWS ID:

View PWS ID TX0950004 on SDWIS

Source: EPA SDWIS Federal Reports Search

State Regulator

Texas Drinking Water Authority

Texas Commission on Environmental Quality (TCEQ) - Drinking Water Watch is the primacy agency that licenses and inspects Plainview Municipal Water System under EPA-delegated authority.

Open TX regulator portal

Source: Texas Commission on Environmental Quality (TCEQ) - Drinking Water Watch

Violation Timeline

Each row links to the EPA SDWIS public record for verification. Cross-reference the contaminant code on EPA's federal report to see violation dates, return-to-compliance status, and enforcement actions.

Year (latest) Contaminant Category Count EPA Record
2017 E. COLI MR 4 SDWIS / TX0950004 / 3014
2010 Coliform (TCR) MCL 7 SDWIS / TX0950004 / 3100
2010 Public Notice Other 3 SDWIS / TX0950004 / 7500
2005 Interim Enhanced Surface Water Treatment Rule MR 1 SDWIS / TX0950004 / 0300
2004 Fluoride MCL 4 SDWIS / TX0950004 / 1025

How Plainview Municipal Water System Compares

Cross-reference this system's record against state averages and the federal MCL framework for context.

Metric Plainview Municipal Water System Texas avg Federal benchmark
Total violations 22 101.5 SDWA compliance, any non-zero count is a recorded breach
Health-based violations 11 22.2 Indicates a contaminant exceeded a federal MCL
PFAS detection 1 compound 93.1% EPA final rule (2024): PFOA/PFOS MCL = 4.0 ppt
Population served 21,104 4,524 Sizing context for compliance burden

Sources: EPA SDWIS and EPA National Primary Drinking Water Regulations (40 CFR Part 141). State averages computed across 7,351 regulated public water systems in Texas.

Federal MCL reference, Safe Drinking Water Act thresholds
Contaminant Federal MCL / Action Level Note
Lead 0 mg/L (Action Level: 0.015 mg/L) Lead and Copper Rule treatment technique
Arsenic 0.010 mg/L (10 ppb) Health-based MCL since 2006
Total Coliform Treatment technique (RTCR) Indicator organism, monitoring trigger
PFOA / PFOS (PFAS) 4.0 ppt each (final 2024 rule) Compliance deadline 2029 (EPA proposed extending to 2031, not yet final as of May 2026)
Nitrate (as N) 10 mg/L Acute health risk for infants

Frequently Asked Questions

Is Plainview Municipal Water System water safe to drink?
Plainview Municipal Water System (PWS ID: TX0950004) has 22 recorded violations in the EPA SDWIS database. PFAS contamination has been detected in UCMR5 testing, with 1 PFAS compound found. This system serves 21,104 people using Surface Water sources.
How many people does Plainview Municipal Water System serve?
Plainview Municipal Water System serves 21,104 people in Plainview, Texas. It is a Local-owned system using Surface Water water sources with 7,328 service connections.
What type of violations does Plainview Municipal Water System have?
Plainview Municipal Water System has 22 total violations: 11 health-based violations (MCL exceedances or treatment failures), 5 monitoring/reporting violations, and 0 treatment technique violations. Health-based violations indicate contaminant levels exceeded EPA safe limits.
Has PFAS been detected in Plainview Municipal Water System water?
Yes. UCMR5 testing detected 1 PFAS compound in Plainview Municipal Water System's water supply: PFBA. PFAS are persistent "forever chemicals" that do not break down in the environment.
What water source does Plainview Municipal Water System use?
Plainview Municipal Water System uses Surface Water as its primary water source. It is classified as a Community Water System (CWS), serving residential populations year-round.
Where does this data come from?
All data comes from the EPA Safe Drinking Water Information System (SDWIS) and the UCMR5 PFAS monitoring program. SDWIS tracks compliance for all public water systems regulated under the Safe Drinking Water Act.
Data Sources: EPA Safe Drinking Water Information System (SDWIS), Q4 2025. PFAS data from EPA UCMR5 monitoring program (2023-2025). This data is provided for informational purposes only.
Data sourced from EPA SDWIS and UCMR5 PFAS monitoring data. See our methodology for details. Retrieved and formatted by PlainWater Editorial

Every figure on PlainWater is rendered directly from EPA SDWIS drinking-water data, no number is typed in by an editor. This system's figures are rendered directly from EPA SDWIS data, no figure is typed in by an editor. See our editorial standards & corrections policy, the methodology behind these numbers, or report a data error.