FORT BLISS MAIN POST AREA
PWS ID: TX0710020 · SAN DIMAS, Texas 91773-1207
FORT BLISS MAIN POST AREA serves 28,000 people in SAN DIMAS, Texas using Groundwater water sources. It has 23 recorded EPA violations, including 3 health-based violations. PFAS "forever chemicals" were detected in UCMR5 testing (3 compounds found).
Water Quality Snapshot: FORT BLISS MAIN POST AREA
FORT BLISS MAIN POST AREA is a private-owned community water system that delivers drinking water to 28,000 residents in SAN DIMAS, Texas (El Paso County) through 4,277 service connections. Its water is drawn from groundwater sources. EPA's Safe Drinking Water Information System records 23 total violations for this system , of which 3 (13%) are health-based — meaning a contaminant exceeded an EPA Maximum Contaminant Level or a required treatment technique failed. A further 8 monitoring and reporting violations are on file. The most recent violation on record dates to 2018.
The most frequently cited contaminant at this system is Chlorine, recorded in 4 violations (MR). Under EPA's UCMR5 PFAS monitoring program, 3 PFAS compounds were detected in samples collected from this system, with a maximum reported concentration of 40.8 ppt. PFAS are persistent synthetic chemicals linked to health effects at very low exposure levels.
Across Texas, EPA tracks 7,351 public water systems serving 33,253,313 people, with 746,210 cumulative violations and 162,945 health-based violations on record. About 90% of systems in the state carry at least one violation, and state-wide the average per system is 101.5 violations. FORT BLISS MAIN POST AREA's 23 violations sit below the Texas average. Statewide, 1,068 of 1,147 UCMR5-tested systems have reported PFAS detections (93.1%). All figures above are sourced directly from EPA SDWIS and UCMR5 public data releases and are updated as EPA publishes new reporting cycles.
3 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.
System Details
- System Type
- Community
- Owner Type
- Private
- Connections
- 4,277
- County
- El Paso
- School/Daycare
- No
- MCL Violations
- 3
- Monitoring Violations
- 8
- Treatment Tech Violations
- 0
Violation History
Contaminant violations recorded by EPA.
| Contaminant | Category | Count | Latest |
|---|---|---|---|
| Chlorine | MR | 4 | 2018 |
| Coliform (TCR) | MR | 3 | 2007 |
| Coliform (TCR) | MCL | 3 | 2008 |
| Public Notice | Other | 2 | 2008 |
| Consumer Confidence Rule | Other | 2 | 2013 |
| Lead and Copper Rule | MR | 1 | 2013 |
PFAS Testing Results (UCMR5)
Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 6 of 120 samples detected PFAS.
| Contaminant | Date | Result | MRL | Status |
|---|---|---|---|---|
| HFPO-DA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| lithium | 7/30/2024 | 34.7000 µg/L | 9 µg/L | Detected |
| 4:2 FTS | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHpS | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFPeS | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| NFDHA | 7/30/2024 | <0.02 µg/L | 0.02 µg/L | Not Detected |
| PFEESA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFMBA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFPeA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| 9Cl-PF3ONS | 7/30/2024 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| 8:2 FTS | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFDA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| 6:2 FTS | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFBA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| ADONA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFOA | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFHxA | 7/30/2024 | 0.0031 µg/L | 0.003 µg/L | Detected |
| PFMPA | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFDoA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFOS | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| PFUnA | 7/30/2024 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| 11Cl-PF3OUdS | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFTA | 7/30/2024 | <0.008 µg/L | 0.008 µg/L | Not Detected |
| PFTrDA | 7/30/2024 | <0.007 µg/L | 0.007 µg/L | Not Detected |
| NMeFOSAA | 7/30/2024 | <0.006 µg/L | 0.006 µg/L | Not Detected |
| PFBS | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHpA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHxS | 7/30/2024 | 0.0037 µg/L | 0.003 µg/L | Detected |
| PFNA | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| NEtFOSAA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFMBA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFDA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFDoA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFHxA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| PFUnA | 7/30/2024 | <0.002 µg/L | 0.002 µg/L | Not Detected |
| 11Cl-PF3OUdS | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| ADONA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| HFPO-DA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFBA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFMPA | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| 6:2 FTS | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| 4:2 FTS | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NEtFOSAA | 7/30/2024 | <0.005 µg/L | 0.005 µg/L | Not Detected |
| PFPeA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NMeFOSAA | 7/30/2024 | <0.006 µg/L | 0.006 µg/L | Not Detected |
| PFEESA | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
| NFDHA | 7/30/2024 | <0.02 µg/L | 0.02 µg/L | Not Detected |
| PFPeS | 7/30/2024 | <0.004 µg/L | 0.004 µg/L | Not Detected |
| lithium | 7/30/2024 | 31.7000 µg/L | 9 µg/L | Detected |
| PFBS | 7/30/2024 | <0.003 µg/L | 0.003 µg/L | Not Detected |
Verify This Water System
The figures above are aggregated from EPA's public databases. To verify the underlying records — or to file a complaint, request a Consumer Confidence Report, or check current monitoring status — go directly to the federal and state regulators that enforce the Safe Drinking Water Act for FORT BLISS MAIN POST AREA.
EPA SDWIS — Federal Reports
EPA's Safe Drinking Water Information System (SDWIS) holds the federal compliance record for every regulated public water system. Open the system-level report by PWS ID:
View PWS ID TX0710020 on SDWISSource: EPA SDWIS Federal Reports Search
Texas Drinking Water Authority
Texas Commission on Environmental Quality (TCEQ) — Drinking Water Watch is the primacy agency that licenses and inspects FORT BLISS MAIN POST AREA under EPA-delegated authority.
Open TX regulator portalSource: Texas Commission on Environmental Quality (TCEQ) — Drinking Water Watch
Violation Timeline
Each row links to the EPA SDWIS public record for verification. Cross-reference the contaminant code on EPA's federal report to see violation dates, return-to-compliance status, and enforcement actions.
| Year (latest) | Contaminant | Category | Count | EPA Record |
|---|---|---|---|---|
| 2018 | Chlorine | MR | 4 | SDWIS / TX0710020 / 0999 |
| 2013 | Consumer Confidence Rule | Other | 2 | SDWIS / TX0710020 / 7000 |
| 2013 | Lead and Copper Rule | MR | 1 | SDWIS / TX0710020 / 5000 |
| 2008 | Coliform (TCR) | MCL | 3 | SDWIS / TX0710020 / 3100 |
| 2008 | Public Notice | Other | 2 | SDWIS / TX0710020 / 7500 |
| 2007 | Coliform (TCR) | MR | 3 | SDWIS / TX0710020 / 3100 |
How FORT BLISS MAIN POST AREA Compares
Cross-reference this system's record against state averages and the federal MCL framework for context.
| Metric | FORT BLISS MAIN POST AREA | Texas avg | Federal benchmark |
|---|---|---|---|
| Total violations | 23 | 101.5 | SDWA compliance — any non-zero count is a recorded breach |
| Health-based violations | 3 | 22.2 | Indicates a contaminant exceeded a federal MCL |
| PFAS detection | 3 compounds | 93.1% | EPA final rule (2024): PFOA/PFOS MCL = 4.0 ppt |
| Population served | 28,000 | 4,524 | Sizing context for compliance burden |
Sources: EPA SDWIS and EPA National Primary Drinking Water Regulations (40 CFR Part 141). State averages computed across 7,351 regulated public water systems in Texas.
Federal MCL reference — Safe Drinking Water Act thresholds ▼
| Contaminant | Federal MCL / Action Level | Note |
|---|---|---|
| Lead | 0 mg/L (Action Level: 0.015 mg/L) | Lead and Copper Rule treatment technique |
| Arsenic | 0.010 mg/L (10 ppb) | Health-based MCL since 2006 |
| Total Coliform | Treatment technique (RTCR) | Indicator organism, monitoring trigger |
| PFOA / PFOS (PFAS) | 4.0 ppt each (final 2024 rule) | Compliance deadline 2029 |
| Nitrate (as N) | 10 mg/L | Acute health risk for infants |
Frequently Asked Questions
Is FORT BLISS MAIN POST AREA water safe to drink? ▼
How many people does FORT BLISS MAIN POST AREA serve? ▼
What type of violations does FORT BLISS MAIN POST AREA have? ▼
Has PFAS been detected in FORT BLISS MAIN POST AREA water? ▼
What water source does FORT BLISS MAIN POST AREA use? ▼
Where does this data come from? ▼
Explore PlainWater
Related Data for Texas
Read our methodology — how this data is sourced, computed, and verified.