PlainWater

CITY OF COPPERAS COVE

PWS ID: TX0500001 · COPPERAS COVE, Texas 76522-2900

PFAS Detected

5 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.

Population Served
37,225
Total Violations
10
Health-Based Violations
3
Water Source
Surface Water

System Details

System Type
Community
Owner Type
Local
Connections
15,044
County
Coryell
School/Daycare
No
MCL Violations
3
Monitoring Violations
4
Treatment Tech Violations
0

Violation History

Contaminant violations recorded by EPA.

Contaminant Category Count Latest
Coliform (TCR) MR 3 1992
TTHM MCL 3 1993
Lead and Copper Rule MR 1 2013
Coliform (TCR) Other 1 1992

PFAS Testing Results (UCMR5)

Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 9 of 120 samples detected PFAS.

Contaminant Date Result MRL Status
9Cl-PF3ONS 8/24/2023 <0.002 µg/L 0.002 µg/L Not Detected
ADONA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
HFPO-DA 8/24/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFHpS 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFBA 8/24/2023 0.0063 µg/L 0.005 µg/L Detected
4:2 FTS 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
8:2 FTS 8/24/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFMPA 8/24/2023 <0.004 µg/L 0.004 µg/L Not Detected
NFDHA 8/24/2023 <0.02 µg/L 0.02 µg/L Not Detected
PFMBA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFEESA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFTrDA 8/24/2023 <0.007 µg/L 0.007 µg/L Not Detected
11Cl-PF3OUdS 8/24/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFPeS 8/24/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFPeA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFHpA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
6:2 FTS 8/24/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFBS 8/24/2023 0.0035 µg/L 0.003 µg/L Detected
NMeFOSAA 8/24/2023 <0.006 µg/L 0.006 µg/L Not Detected
PFUnA 8/24/2023 <0.002 µg/L 0.002 µg/L Not Detected
PFTA 8/24/2023 <0.008 µg/L 0.008 µg/L Not Detected
lithium 8/24/2023 <9 µg/L 9 µg/L Not Detected
PFHxS 8/24/2023 0.0043 µg/L 0.003 µg/L Detected
PFNA 8/24/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFOS 8/24/2023 0.0041 µg/L 0.004 µg/L Detected
PFOA 8/24/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFDA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFDoA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFHxA 8/24/2023 <0.003 µg/L 0.003 µg/L Not Detected
NEtFOSAA 8/24/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFHxS 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
NEtFOSAA 5/23/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFTA 5/23/2024 <0.008 µg/L 0.008 µg/L Not Detected
PFTrDA 5/23/2024 <0.007 µg/L 0.007 µg/L Not Detected
PFMPA 5/23/2024 <0.004 µg/L 0.004 µg/L Not Detected
lithium 5/23/2024 <9 µg/L 9 µg/L Not Detected
PFHpS 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFPeS 5/23/2024 <0.004 µg/L 0.004 µg/L Not Detected
NFDHA 5/23/2024 <0.02 µg/L 0.02 µg/L Not Detected
PFEESA 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFPeA 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
8:2 FTS 5/23/2024 <0.005 µg/L 0.005 µg/L Not Detected
4:2 FTS 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
6:2 FTS 5/23/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFBA 5/23/2024 <0.005 µg/L 0.005 µg/L Not Detected
HFPO-DA 5/23/2024 <0.005 µg/L 0.005 µg/L Not Detected
ADONA 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFOS 5/23/2024 <0.004 µg/L 0.004 µg/L Not Detected
PFMBA 5/23/2024 <0.003 µg/L 0.003 µg/L Not Detected
9Cl-PF3ONS 5/23/2024 <0.002 µg/L 0.002 µg/L Not Detected
Data Sources: EPA Safe Drinking Water Information System (SDWIS), Q4 2025. PFAS data from EPA UCMR5 monitoring program (2023-2025). This data is provided for informational purposes only.