PlainWater

FORT DRUM

PWS ID: NY2212214 · FORT DRUM, New York 13602

PFAS Detected

6 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.

Population Served
34,000
Total Violations
19
Health-Based Violations
14
Water Source
Surface Water

System Details

System Type
Community
Owner Type
Federal
Connections
1,750
County
Jefferson
School/Daycare
No
MCL Violations
14
Monitoring Violations
3
Treatment Tech Violations
0

Violation History

Contaminant violations recorded by EPA.

Contaminant Category Count Latest
TTHM MCL 11 2017
Coliform (TCR) MCL 3 2010
Lead and Copper Rule MR 3 2013

PFAS Testing Results (UCMR5)

Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 12 of 180 samples detected PFAS.

Contaminant Date Result MRL Status
PFDA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFDoA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
4:2 FTS 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFUnA 8/13/2024 <0.002 µg/L 0.002 µg/L Not Detected
PFOA 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
ADONA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
HFPO-DA 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFHxA 8/13/2024 0.0120 µg/L 0.003 µg/L Detected
PFBA 8/13/2024 0.0070 µg/L 0.005 µg/L Detected
6:2 FTS 8/13/2024 0.0130 µg/L 0.005 µg/L Detected
11Cl-PF3OUdS 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
9Cl-PF3ONS 8/13/2024 <0.002 µg/L 0.002 µg/L Not Detected
8:2 FTS 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFMPA 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
PFPeA 8/13/2024 0.0250 µg/L 0.003 µg/L Detected
PFOS 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
PFTrDA 8/13/2024 <0.007 µg/L 0.007 µg/L Not Detected
NEtFOSAA 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFMBA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
NMeFOSAA 8/13/2024 <0.006 µg/L 0.006 µg/L Not Detected
PFTA 8/13/2024 <0.008 µg/L 0.008 µg/L Not Detected
PFBS 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFEESA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
NFDHA 8/13/2024 <0.02 µg/L 0.02 µg/L Not Detected
PFPeS 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
PFHpS 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
lithium 8/13/2024 <9 µg/L 9 µg/L Not Detected
PFHpA 8/13/2024 0.0040 µg/L 0.003 µg/L Detected
PFHxS 8/13/2024 0.0030 µg/L 0.003 µg/L Detected
PFNA 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
9Cl-PF3ONS 8/13/2024 <0.002 µg/L 0.002 µg/L Not Detected
NMeFOSAA 8/13/2024 <0.006 µg/L 0.006 µg/L Not Detected
PFMBA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFEESA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFUnA 8/13/2024 <0.002 µg/L 0.002 µg/L Not Detected
NFDHA 8/13/2024 <0.02 µg/L 0.02 µg/L Not Detected
PFBS 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFPeS 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
PFHpS 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
PFTA 8/13/2024 <0.008 µg/L 0.008 µg/L Not Detected
NEtFOSAA 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFPeA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
lithium 8/13/2024 <9 µg/L 9 µg/L Not Detected
PFMPA 8/13/2024 <0.004 µg/L 0.004 µg/L Not Detected
8:2 FTS 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFHpA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
6:2 FTS 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
PFBA 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
HFPO-DA 8/13/2024 <0.005 µg/L 0.005 µg/L Not Detected
ADONA 8/13/2024 <0.003 µg/L 0.003 µg/L Not Detected
Data Sources: EPA Safe Drinking Water Information System (SDWIS), Q4 2025. PFAS data from EPA UCMR5 monitoring program (2023-2025). This data is provided for informational purposes only.