PlainWater

FLORIDA GOVERNMENTAL UTILITY AUTHORITY

PWS ID: FL5360172 · LONGWOOD, Florida 32779

PFAS Detected

4 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.

Population Served
32,296
Total Violations
43
Health-Based Violations
17
Water Source
Groundwater

System Details

System Type
Community
Owner Type
Private
Connections
13,981
County
Lee
School/Daycare
No
MCL Violations
17
Monitoring Violations
25
Treatment Tech Violations
0

Violation History

Contaminant violations recorded by EPA.

Contaminant Category Count Latest
E. COLI MR 16 2025
TTHM MCL 8 2007
TTHM MR 5 2007
Gross Alpha, Excl. Radon and U MCL 3 1992
Coliform (TCR) MCL 3 1991
Total Haloacetic Acids (HAA5) MR 3 2008
Revised Total Coliform Rule MCL 3 2018
Coliform (TCR) MR 1 2006

PFAS Testing Results (UCMR5)

Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 7 of 60 samples detected PFAS.

Contaminant Date Result MRL Status
PFDA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
9Cl-PF3ONS 9/25/2023 <0.002 µg/L 0.002 µg/L Not Detected
11Cl-PF3OUdS 9/25/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFUnA 9/25/2023 <0.002 µg/L 0.002 µg/L Not Detected
PFHxA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFDoA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
ADONA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFOA 9/25/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFOS 9/25/2023 0.0123 µg/L 0.004 µg/L Detected
PFNA 9/25/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFHxS 9/25/2023 0.0043 µg/L 0.003 µg/L Detected
PFHpA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFBS 9/25/2023 0.0035 µg/L 0.003 µg/L Detected
NFDHA 9/25/2023 <0.02 µg/L 0.02 µg/L Not Detected
HFPO-DA 9/25/2023 <0.005 µg/L 0.005 µg/L Not Detected
lithium 9/25/2023 <9 µg/L 9 µg/L Not Detected
PFPeS 9/25/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFMBA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFBA 9/25/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFHpS 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFEESA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
8:2 FTS 9/25/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFPeA 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFMPA 9/25/2023 <0.004 µg/L 0.004 µg/L Not Detected
4:2 FTS 9/25/2023 <0.003 µg/L 0.003 µg/L Not Detected
6:2 FTS 9/25/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFDoA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
9Cl-PF3ONS 3/22/2023 <0.002 µg/L 0.002 µg/L Not Detected
11Cl-PF3OUdS 3/22/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFUnA 3/22/2023 <0.002 µg/L 0.002 µg/L Not Detected
PFHxA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
HFPO-DA 3/22/2023 <0.005 µg/L 0.005 µg/L Not Detected
ADONA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFDA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFOA 3/22/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFOS 3/22/2023 0.0112 µg/L 0.004 µg/L Detected
PFNA 3/22/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFHpA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFBS 3/22/2023 0.0055 µg/L 0.003 µg/L Detected
PFBA 3/22/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFHxS 3/22/2023 0.0036 µg/L 0.003 µg/L Detected
PFMBA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
NFDHA 3/22/2023 <0.02 µg/L 0.02 µg/L Not Detected
NEtFOSAA 3/22/2023 <0.005 µg/L 0.005 µg/L Not Detected
PFPeS 3/22/2023 <0.004 µg/L 0.004 µg/L Not Detected
PFEESA 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
PFHpS 3/22/2023 <0.003 µg/L 0.003 µg/L Not Detected
lithium 3/22/2023 <9 µg/L 9 µg/L Not Detected
NMeFOSAA 3/22/2023 <0.006 µg/L 0.006 µg/L Not Detected
PFTA 3/22/2023 <0.008 µg/L 0.008 µg/L Not Detected
Data Sources: EPA Safe Drinking Water Information System (SDWIS), Q4 2025. PFAS data from EPA UCMR5 monitoring program (2023-2025). This data is provided for informational purposes only.