City of Arroyo Grande Utilities Division

Operator location Arroyo Grande, California - 29% of 7 violations are health-based (upper-third health share (> 23%)); surface water source; 17,963 served per SDWIS.

17,963
People served (this PWS)
7
EPA violations (this PWS)
2
Health-based (this PWS)
6 PFAS
UCMR5 (this PWS)
Follow published updates (RSS)

City of Arroyo Grande Utilities Division standing, low SDWIS violation third

29% of 7 recorded violations are health-based - upper-third health share (> 23%). Corpus terciles use 29,740 systems serving 500+ (the sitemap cohort). Health-based share 29% is upper-third health share (> 23%). UCMR5: upper-third PFAS panel (> 4 compounds). Population rank #2,978 of 29,740 among systems serving 500+.

The verdict

City of Arroyo Grande Utilities Division is in the lower third by violation count (7; lower-third violation load (≤ 21 violations)). A low count does not mean the system is unmonitored - monitoring and reporting violations still appear in SDWIS. Population served is large (17,963; larger served population (> 3,309)), so household exposure scale sits behind the violation mix. Health-based share is 29% - most of this ledger is MCL or treatment-technique exceedance. UCMR5 detected 6 PFAS compounds (upper-third PFAS panel (> 4 compounds)).

#2,978 of 29,740
Population · /systems
#371 of 1,701
Population · CA
7
Total EPA violations on record
29%
Health-based (MCL / treatment failure)

Population ordinals match the sitemap cohort (systems serving 500+, population_served DESC). See methodology · corpus placement.

PFAS Detected

6 PFAS "forever chemicals" detected in testing under EPA's UCMR5 monitoring program.

System Details

System Type
Community
Owner Type
Local
Connections
6,854
County
San Luis Obispo
School/Daycare
No
MCL Violations
2
Monitoring Violations
3
Treatment Tech Violations
0

Violation History

Contaminant violations recorded by EPA.

Contaminant Category Count Latest
Nitrate MR 2 2012
TTHM MCL 2 1996
Revised Total Coliform Rule MON 1 2025

Violation Count vs. the National Corpus

City of Arroyo Grande Utilities Division has 7 recorded EPA violations, 13% of the 29,740 public water systems serving 500+ people nationwide carry fewer, and 85% carry more. 29% of this system's own violations are health-based (2 of 7), and it ranks #2,978 of 29,740 by population served among that same cohort.

EPA violations vs. the national water-system corpus

Public water systems serving 500+ people (EPA SDWIS)

7 Among the lowest violation counts fewer violations than 85% of 29,740 water systems

the national water-system corpus, bucketed by value

Each bar is a band; taller bars hold more water systems. The dashed line + filled bar mark this entry. Hover or tap any bar for its full count and share, and where it sits relative to this entry.

Source EPA SDWIS · 2026-05-15

PFAS Testing Results (UCMR5)

Results from EPA's Fifth Unregulated Contaminant Monitoring Rule. 21 of 232 samples detected PFAS.

Contaminant Date Result MRL Status
11Cl-PF3OUdS 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
PFUnA 9/10/2024 <2.00 ppt 2.00 ppt Not Detected
PFHxA 9/10/2024 3.30 ppt 3.00 ppt Detected
PFDoA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFOA 9/10/2024 4.60 ppt 4.00 ppt Detected
PFNA 9/10/2024 <4.00 ppt 4.00 ppt Not Detected
PFHxS 9/10/2024 4.30 ppt 3.00 ppt Detected
PFBS 9/10/2024 11.00 ppt 3.00 ppt Detected
9Cl-PF3ONS 9/10/2024 <2.00 ppt 2.00 ppt Not Detected
PFDA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFHpA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
NFDHA 9/10/2024 <20.00 ppt 20.00 ppt Not Detected
NEtFOSAA 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
NMeFOSAA 9/10/2024 <6.00 ppt 6.00 ppt Not Detected
PFOS 9/10/2024 5.60 ppt 4.00 ppt Detected
ADONA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFTA 9/10/2024 <8.00 ppt 8.00 ppt Not Detected
PFPeS 9/10/2024 <4.00 ppt 4.00 ppt Not Detected
PFTrDA 9/10/2024 <7.00 ppt 7.00 ppt Not Detected
PFEESA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFMBA 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
4:2 FTS 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFMPA 9/10/2024 <4.00 ppt 4.00 ppt Not Detected
8:2 FTS 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
HFPO-DA 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
PFBA 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
PFPeA 9/10/2024 3.30 ppt 3.00 ppt Detected
6:2 FTS 9/10/2024 <5.00 ppt 5.00 ppt Not Detected
PFHpS 9/10/2024 <3.00 ppt 3.00 ppt Not Detected
PFMBA 6/19/2024 <3.00 ppt 3.00 ppt Not Detected
PFHpS 6/19/2024 <3.00 ppt 3.00 ppt Not Detected
11Cl-PF3OUdS 6/19/2024 <5.00 ppt 5.00 ppt Not Detected
NFDHA 6/19/2024 <20.00 ppt 20.00 ppt Not Detected
PFOS 6/19/2024 6.80 ppt 4.00 ppt Detected
PFEESA 6/19/2024 <3.00 ppt 3.00 ppt Not Detected
PFBS 6/19/2024 11.00 ppt 3.00 ppt Detected
PFHxS 6/19/2024 5.50 ppt 3.00 ppt Detected
PFOA 6/19/2024 5.80 ppt 4.00 ppt Detected
PFHxA 6/19/2024 3.50 ppt 3.00 ppt Detected
PFUnA 6/19/2024 <2.00 ppt 2.00 ppt Not Detected
9Cl-PF3ONS 6/19/2024 <2.00 ppt 2.00 ppt Not Detected
ADONA 6/19/2024 <3.00 ppt 3.00 ppt Not Detected
HFPO-DA 6/19/2024 <5.00 ppt 5.00 ppt Not Detected
PFPeA 6/19/2024 4.10 ppt 3.00 ppt Detected
PFTA 6/19/2024 <8.00 ppt 8.00 ppt Not Detected
NMeFOSAA 6/19/2024 <6.00 ppt 6.00 ppt Not Detected
PFTrDA 6/19/2024 <7.00 ppt 7.00 ppt Not Detected
PFPeS 6/19/2024 <4.00 ppt 4.00 ppt Not Detected
PFMPA 6/19/2024 <4.00 ppt 4.00 ppt Not Detected
PFNA 6/19/2024 <4.00 ppt 4.00 ppt Not Detected

Health-based violations on City of Arroyo Grande Utilities Division

2 health-based rows in the tables above map to MCL or treatment-technique exceedances, verify each contaminant code on the federal SDWIS report for CA4010001.

Sources: EPA SDWIS · California State Water Resources Control Board, Division of Drinking Water

Nationwide peers

7 violations · 17,963 served: nearest cross-state SDWIS matches.

What to do with City of Arroyo Grande Utilities Division

Use this system's EPA-reported record as a starting filter, not a final verdict.

  • See how every tracked system in California compares on the same EPA violation measures. California systems
  • Check whether PFAS was detected at this system under UCMR5 testing. PFAS guide
  • Find and compare another public water system by name or PWSID. Search systems

EPA SDWIS and UCMR5 figures are informational only, not a substitute for a certified lab test of your own tap water.

Data sourced from EPA SDWIS and UCMR5 PFAS monitoring data. See our methodology for details. Retrieved and formatted by PlainWater